Final | 9/11/2019 | 9/12/2019 | 9/12/2019 | A | PASS |
James Ady
|
|
|
jIM Phone #: ###-#### Corrections made final ok
|
Final | 9/5/2019 | 9/5/2019 | 9/5/2019 | P | FAIL |
James Ady
|
|
|
Jim Phone #: ###-#### 406.12. Garage receps shall be tamper resistant. 210.8. Garage welder recep shall be GFCI protected. 406.9 A/C service recep shall be type W/R. 110.3 Bath GFCI wired incorrectly. Note: remodel situation, AFCI recep ok to protect Master Bed. Did not hot check bed receps. Painters had walls masked and were painting at time of inspection
|
Electrical Rough-In | 7/30/2019 | 7/31/2019 | 7/31/2019 | A | PASS |
James Ady
|
|
|
Call for access- Jim Phone #: ###-#### corrections made rough in ok
|
Electrical Rough-In | 7/29/2019 | 7/30/2019 | 7/30/2019 | A | FAIL |
James Ady
|
|
|
Jim Phone #: ###-#### 240.4D4 Max ampacity for 14 awg wire is 15amps. (Minisplit has a 16.5 amp minimum.) 300.4A1 Wire through bored holes less than 1 1/4in from face shall be protected.(Nail plates need in misc. places on top plates) 314.16. Box fill. (Master bed homerun box overfilled. Need 21.5 min box.) 210.63 A/C equipment recep. (Service recep needed within 25ft of Mini split condenser)
|
Conference | 6/27/2019 | 6/28/2019 | 6/28/2019 | A | PASS |
James Ady
|
|
|
Jim Phone #: ###-#### Project is in early stages.(no walls stood, no roof) Owner has electrical back ground. Will box and drill over 4th of July weekend. Has Home owner handout. Will call for another conference when closer to pulling wire.
|