Permanent Service | 6/7/2019 | 6/7/2019 | 6/7/2019 | P | CANC |
Tom Saunders
|
|
|
Please arrive before 3:00 as no one will be available after 3:00 at the residence
Phone #: ###-#### Inspection requested via web by Eric Schroeder needed to be a final inspection
|
Final | 6/7/2019 | 6/7/2019 | 6/7/2019 | P | PASS |
Tom Saunders
|
|
|
Please arrive before 3:00 as no one will be available after 3:00 at the residence
Phone #: ###-#### Inspection requested via web by Eric Schroeder.... At time of inspection wire for hot tub and breaker for hot tub in panel have been removed ok to final
|
Rough-In Permanent Service | 6/5/2019 | 6/5/2019 | 6/5/2019 | P | PASS |
Tom Saunders
|
|
|
Please let me know when inspection is complete so I can call Idaho Power to reconnect power ###-#### Kathy @Eco Electric Phone #: ###-#### Inspection requested via web by Eric Schroeder... 100A panel replaced existing 100A panel additional ground rod added existing 50A hot tub circuit installed with no inspection previous to permit for service change pulled requiring electrician remove hot tub circuit out of panel and permit will not be finaled until hot tub circuit is completely removed or a service upgrade to minimum 200A is done house is being rented at this time p/s u/g reconnect ok
|