Final | 7/23/2019 | 7/24/2019 | 7/24/2019 | A | PASS |
Tom Saunders
|
|
|
Chad Vanorden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce... 240V outlet within 6ft of sink removed and box blanked off at final
|
Final | 7/22/2019 | 7/22/2019 | 7/22/2019 | P | FAIL |
Tom Saunders
|
|
|
Chad Vanorden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce.... 1) all receptacles within 6ft of sink shall have GFCI protection...unable to verify 240V outlet in breakroom 2) access for HVAC disconnect above grid shall have access...unable to verify
|
Electrical Rough-In | 7/1/2019 | 7/2/2019 | 7/2/2019 | A | PASS |
Tom Saunders
|
|
|
Ceiling Inspection, Chad Vanorden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce... grid ok to cover access for disconnect above grid needs provided..at entrance...check at final
|