Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberELE19-02136
StatusFinaled
Name LOTT ELECTRIC INC
Site Address 110 W MAIN ST
Project Name110 Main Street Basement
Customer Number110 Main S
ePlanReviewNo
Description
Alteration: Basement remodel. All conduit and wring for electrical system.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/13/20201/13/20201/13/2020PCANC
DetailsRock A. Hudson
ronald Phone #: ###-####
Duplicate request
Final1/10/20201/13/20201/13/2020APASS
DetailsRock A. Hudson
Final please. Have a bless day! Phone #: ###-#### Inspection requested via web by Kyle Lott
Notches cut into duct work to bew patched maintaining access to boxes. Final ok
Final1/8/20201/9/20201/9/2020AFAIL
DetailsRock A. Hudson
Final please. Have a bless day Phone #: ###-#### Inspection requested via web by Kyle Lott
At Building inspectors request need to address work done under ELE16-02769. This permit expired 5-14-19, a new permit shall be pulled covering this work and an inspection must be performed for this work. Called Kyle's number and left information with his receptionist.
110.3- Baseboard manufactureres instructions states receptacles shall not be located above baseboard heaters. 1 in down office.
210.8- GFCI receptacle devices shall be located where readily accessible. In drinking fountains.
314.29- Ceiling boxes shall be located where accessible. HVAC duct covering misc boxes rendering them not accessible.
Electrical Rough-In11/18/201911/19/201911/19/2019PPASS
DetailsRock A. Hudson
Rough in please. Thank you. Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott
Basement walls and bathroom hardlid rough in ok cover
Electrical Rough-In6/12/20196/13/20196/13/2019AFAIL
DetailsRock A. Hudson
Maria Phone #: ###-####
Although moritorium has been lifted to pull building permits the building permit still shall complete plan review and be issued prior to performing work associated with area under building permit. Recall when bulding permit has been issued