Permit Information
Permit NumberELE19-02150
StatusFinaled
Name ALL-STAR ELECTRIC
Site Address 4776 N FIVE MILE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Ti remodel for dental clinic
Ready for wall rough in
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/15/20198/15/20198/15/2019PPASS
DetailsTom Saunders
Corrections made building is open Phone #: ###-#### Inspection requested via web by Kevin Oderkirk...corrections made...ok to final
Final8/14/20198/14/20198/14/2019PFAIL
DetailsRock A. Hudson
Building is open Phone #: ###-#### Inspection requested via web by Kevin Oderkirk 110.3- 2 receptacles not working in imaging room.
210.8(B)- In other than dwelling units 120 volt, 15 and 20 amp receptacles located with in 6' of a sink shall have GFCI protection. Refer receptacle and exam rm receptacles.
406.12(5)- Tamper resistant receptacles shall be installed in business offices, corridors, waiting rooms and similar areas.
Electrical Rough-In7/19/20197/19/20197/22/2019PPASS
DetailsDaryl DeGrange
rough-in ok cover ceiling grid
Electrical Rough-In6/12/20196/12/20196/12/2019PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Kevin Oderkirk...
suite 103
rough new walls only ok to cover
will need verification that reduntant ground installed in existing outlets in exam rm exterior walls at next rough-in inspection