Final | 11/3/2019 | 11/4/2019 | 11/4/2019 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|
Permanent Service | 10/28/2019 | 10/29/2019 | 10/28/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 2 grounding electrode conductors leave panel but wireman could not verify where. Asked to supplement with an additional ground rod as per 250.53 prior to power swing. Will verify on final. p/s o/h n ok
|
Rough-In Permanent Service | 6/25/2019 | 6/26/2019 | 6/26/2019 | A | CANC |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI
|
Electrical Rough-In | 6/26/2019 | 6/26/2019 | 6/26/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Garage converted to 2 beds, bath, Laundry rm, and kitchen, dining. Corrections made rough in ok
|
Electrical Rough-In | 6/16/2019 | 6/17/2019 | 6/17/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. No nail plates found several locations needed. Shallow holes and 45 degree corners.
|