Final | 9/17/2019 | 9/17/2019 | 9/17/2019 | A | PASS |
James Ady
|
|
|
garage code 1957 Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
|
Final | 9/17/2019 | 9/17/2019 | 9/17/2019 | A | CANC |
James Ady
|
|
|
Garage Code 1957 Phone #: ###-#### >> Inspection requested via web by Therrin Robertson Inspection cancelled from web by: Therrin Robertson
|
Rough-In Permanent Service | 7/11/2019 | 7/11/2019 | 7/11/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 7/10/2019 | 7/10/2019 | 7/10/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 110.3- Expansion joint shall be installed as per manufacturers instructions. At time of install joint shall be opened to mid point to allow for expansion and contraction. 110.14- Connection to concrete encased electode shall be tight. moved with fingers. 250.148- Metal boxes shall be connected to equipment grounding conductors. All equipment grounding conductors in a box shall be connected together. Complete make up. 300.15- All NM cables shall terminate in a box. Up bed smoke detector. 312.5(A)- Unused openings in meter base shall be closed by approved means. 2" KO open. 590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protection. 250 in temp pole failed test.
|