Complete Installation (includes room count and per: New house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/28/20201/29/20201/29/2020APASS
DetailsJames Ady
garage code 5706 Phone #: ###-#### Inspection requested via web by Neal Rumsey Corrections made final ok
Final1/24/20201/24/20201/24/2020AFAIL
DetailsJames Ady
garage code 5706 Phone #: ###-#### Inspection requested via web by Neal Rumsey 210.8 Recep within 6ft of sink shall be GFCI protected (Down hall recep in front of wet bar) 210.52DEach sink basin shall have recep within 3ft and on adjacent wall(Up bed NW corner Vanity) 110.3 Master bed stack switch installed wrong. (Up is off Dn is on, check wiring)
Electrical Rough-In11/6/201911/6/201911/6/2019APASS
DetailsJames Ady
Master Bathroom floor heat. garage code. 5706 Phone #: ###-#### Inspection requested via web by Neal Rumsey floor heat only ok
Rough-In Permanent Service6/27/20196/27/20196/27/2019PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Neal Rumsey corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service6/24/20196/25/20196/25/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
110.3- Recessed can junction box covers shall be completely installed as per instructions. Kitchen, master bed, pinched wire in up bed.
250.148- Epuipment grounding conductors shall be bonded to metal boxes. net panels.
300.4- Nail plate SER at upper wall in basement.
300.15- NM cables shall terminate in a box. Dining box not stuffed.
314.17- KO seal needed for unused hole in service panel.
314 20- All boxes shall have covers. Recessed coan cover missing in up bathroom.
334.30- NM cable shall be secured with in 12" of 2 gang in down bed.
408.7- Unused breaker spaces shall be closed by approved means. Service panel.
590.6(B)- Receptacles other than 120 volt used for construction shall have GFCI protection. Temp pole 250 will not trip.