Permit Information
Permit NumberELE19-02523
StatusFinaled
Name SZURGOT ELECTRIC
Site Address 2004 N 9TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: New 200 amp overhead service, whole house remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/19/201911/19/201911/19/2019PPASS
DetailsMark Moncarr
code to get in is 0-1-2 Phone #: ###-#### Inspection requested via web by Barbara Szurgot Ok final.
Electrical Rough-In10/1/201910/2/201910/2/2019APASS
DetailsMark Moncarr
There are 2 floor heat locations to inspect. Phone #: ###-#### Inspection requested via web by Barbara Szurgot Ok cover flr heat 2 baths main level.
Rough-In Permanent Service7/18/20197/18/20197/18/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Addition Rough in ok cover p/s o/h rec ok
Rough-In Permanent Service7/16/20197/17/20197/17/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
110.14(D)- Grounding electrode termination in meter panel combo shall be torqued to spec. Termination in panel loose.
210.52(C)- Area to right of range is new counter top space in kitchen and shall have receptacle outlets installed.
250.110- Short runs of flexible metal conduit shall be bonded to equiment grounding conductor or terminate to a box with equipment grounding conductor terminated within. Floor heat boxes.
300.4- Where NM cable is run thru holes or channels that do not maintain 1 1/4" from framing surface they shall be protected from physical damage by nail plates or raceways.
408.7- Unused breaker spaces shall be closed by approved means prior to being energized.