Final | 12/10/2019 | 12/10/2019 | 12/10/2019 | P | PASS |
Tom Saunders
|
|
|
Please call when you are in route. Phone #: ###-#### Inspection requested via web by Spencer McLean...service panel complete...ok to final
|
Permanent Service | 10/8/2019 | 10/8/2019 | 10/8/2019 | P | PASS |
Tom Saunders
|
|
|
Please call when in route. Phone #: ###-#### Inspection requested via web by Spencer McLean...corrections made...p/s u/g new ok
|
Permanent Service | 9/30/2019 | 10/1/2019 | 10/1/2019 | A | FAIL |
Tom Saunders
|
|
|
Please call when you are in route. Phone #: ###-#### Inspection requested via web by Spencer McLean... 1)available fault current label needs applied before power can be given 2) 2nd ground rod needs verified for service...found only 1
|
Electrical Rough-In | 7/16/2019 | 7/17/2019 | 7/17/2019 | P | PASS |
Tom Saunders
|
|
|
Spencer Phone #: ###-####...work location behind baseball field..verified 4" pipe for fiber...18" deep...just for notes to permit...electrical work will be called in at later date for inspection once ready
|