Final | 7/26/2019 | 7/29/2019 | 7/29/2019 | A | PASS |
Tom Saunders
|
|
|
Call ahead // Brian Phone #: ###-####... correction made...ok to final
|
Final | 7/24/2019 | 7/26/2019 | 7/26/2019 | A | FAIL |
James Ady
|
|
|
Please inspect connection of mini split A/C Phone #: ###-#### Inspection requested via web by Kendra Lanham 440.21C Protective device shall not exceed manufacturer's values. ( was unable to gain access to house to see panel. Spoke to electrician, Said he installed 20A breaker. Nameplate is 15A max) Re-call after breaker is replaced and schedule with owner
|