Permit Information
Permit NumberELE19-02841
StatusFinaled
Name LOTT ELECTRIC INC
Site Address 6401 S EISENMAN RD Unit: UNIT 101
Project Name 
Customer NumberAll Valley
ePlanReviewNo
Description
Alteration: Tenant improvement: LED fixtures, 1 outlet upstairs and 1 downstairs, wiring, labor.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/10/20199/10/20199/10/2019PPASS
DetailsJames Ady
Electrical final please. Thank you and have a bless day!!! Phone #: ###-#### Inspection requested via web by Kyle Lott Final ok
Rough-In Permanent Service9/10/20199/10/20199/10/2019PPASS
DetailsJames Ady
Electrical final please. Thank you and have a bless day!!! Phone #: ###-#### Inspection requested via web by Kyle Lott Rough in ok
Final9/6/20199/6/20199/6/2019PFAIL
DetailsRock A. Hudson
Final inspection please. Thank you! Phone #: ###-#### Inspection requested via web by Kyle Lott
300.15- All cables shall terminate in a box. Upstairs MC up thru floor with 5' of loose wire and open stripped ends exposed.
314.25- All boxes shall have covers. Open junction box in ceiling against wall. Open switch box
330.30- MC shall be secured with in 12" of a box. Couple locations.
Electrical Rough-In7/30/20197/31/20197/31/2019APASS
DetailsEric Story
Electrical rough in please. Thank you. Have a bless day! Phone #: ###-#### Inspection requested via web by Kyle Lott
Upstairs area ok to cover. No floor outlet at this time until they decide to change area to conference room in the future...