Permit Information
Permit NumberELE19-02902
StatusFinaled
Name DAVID MCCLELLAN CONTRACTING
Site Address 421 S CURTIS RD Unit: 108
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Complete wiring of new single level 3 bedroom, 2 bath home including meter base and service
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/20/20207/20/20207/20/2020PPASS
DetailsTom Saunders
call for door code. Phone #: ###-#### Inspection requested via web by David McClellan...ok to final
Electrical Rough-In10/21/201910/22/201910/22/2019APASS
DetailsDaryl DeGrange
trench out front only Phone #: ###-#### Inspection requested via web by David McClellan R/I ok cover trench to post light
Electrical Rough-In10/15/201910/15/201910/15/2019PFAIL
DetailsTom Saunders
trench depth for monument light direct bury wire Phone #: ###-#### Inspection requested via web by David McClellan...
1) UF wire needs trench to proper depth...T300.5
Rough-In Permanent Service8/23/20198/23/20198/23/2019APASS
DetailsTom Saunders
corrections made
rough ok to cover
p/s u/g new ok
Electrical Rough-In8/21/20198/22/20198/22/2019AFAIL
DetailsTom Saunders
Whole house and service Phone #: ###-#### Inspection requested via web by David McClellan...

**as per permit ELE19-01739..house accross street...UF wire installedwith no inspection...needs addressed**

1) all wires shall have a connector or attachment where enters box...bell box side of house...lot #108 and #113 accross street
2) 12/2 NMB and 14/2 NMB in same box and feeding a completed circuit...unable to verify circuit size and location in panel
3) nail plates required...mst bed switches and back door in dining...top plate
4) stack-it used to support/strap 8/3 NMB...exceeds manufacturers rating...12 and 14 NMB only
5) all metal boxes shall be grounded...LV panel