Final | 12/19/2019 | 12/19/2019 | 12/19/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson final ok
|
Final | 11/22/2019 | 11/25/2019 | 11/25/2019 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson... 1) overhead service needs guide wire kit installed...230.28 2) bracing is required for masts that exceed 30" Idaho Power requirement as well
|
Rough-In Permanent Service | 8/23/2019 | 8/26/2019 | 8/26/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson.... rough ok to cover p/s o/h relocate ok
|
Rough-In Permanent Service | 8/6/2019 | 8/7/2019 | 8/7/2019 | A | FAIL |
Tom Saunders
|
|
|
Garage addition Phone #: ###-#### Inspection requested via web by Zane Robertson.. 1) verify wire used in over head service is rated to be used 2) all-in-one used for new service shall be installed using manufacturer's instructions...busing not rated for installed breakers 3) extertior main service needs labelling
|