Final | 10/31/2019 | 11/1/2019 | 11/1/2019 | A | PASS |
Tom Saunders
|
|
|
Call Kevin ###-#### to meet you or give you access info. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan... corrections made...ok to final
|
Final | 10/30/2019 | 10/31/2019 | 10/31/2019 | A | FAIL |
Tom Saunders
|
|
|
Please call Kevin ###-#### to meet you there or for access info. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan..
1) all 120V outlets in garage shall have GFCI protection 2) 120/240V outlets in garage shall be completely installed...plates OUTLETS MOVED IN GARAGE FOR WASHER AND DRYER 3) outside disconnects need proper labelling as too what breaker in panel is its OCPD 4) outlets for pantry counter need installed-no point along counter top wall line shall be more than 2ft without an outlet..210.52(C)(1)
|
Electrical Rough-In | 8/9/2019 | 8/12/2019 | 8/12/2019 | A | PASS |
Tom Saunders
|
|
|
Call Kevin ###-#### to meet you there. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan... rough in of kitchen, new butlers pantry, and bonus rm with laundry ok to cover excluding back wall of bonus rm-new and existing mini splits wiring needs addressed
|