Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-02994
StatusIssued
Name BENCHMARK ELECTRIC CO
Site Address 900 E PARK BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: run/wire external conduits, install disconnect. Small cell-Electrical work only. Alteration for Antennae/ cellular.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service9/19/20199/19/20199/19/2019PPASS
DetailsJames Ady
gate code 2914. Any questions feel free to call Jason at ###-#### Phone #: ###-#### Inspection requested via web by Sherry Allen Corrections made Grounding Veryfied p/s u/g n ok
Permanent Service9/5/20199/6/20199/6/2019AFAIL
DetailsRock A. Hudson
this is a service inspection. Padlock #2914. Any questions feel free to call Jason at ###-#### Phone #: ###-#### Inspection requested via web by Sherry Allen
250.24- AC system shall have a grounding electrode conductor connected to the grounded conductor. Unable to verify grounding electrode and main bonding jumper missing to bond grounded conductor.