Final | 11/1/2019 | 11/4/2019 | 11/4/2019 | A | PASS |
Tom Saunders
|
|
|
Call Roderick for access Phone #: ###-#### Inspection requested via web by David Green.. corrections made...ok to final
|
Final | 10/28/2019 | 10/29/2019 | 10/29/2019 | A | FAIL |
Tom Saunders
|
|
|
Number is the General for access Phone #: ###-#### Inspection requested via web by David Green... 1) main panel shall be properly and clear labelling to specific purpose and use..408.4 This was discussed at rough-in time!!! 2) kitchen counter outlets shall have GFCI protection..210.8(A)(6) 3) no point a long counter top wall line shall be more then 2 ft without an outlet..210.52(C)(1)
|
Electrical Rough-In | 8/15/2019 | 8/16/2019 | 8/16/2019 | A | PASS |
Tom Saunders
|
|
|
Corrections made Phone #: ###-#### Inspection requested via web by David Green...ok
|
Electrical Rough-In | 8/14/2019 | 8/15/2019 | 8/15/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David Green... gave approval for cover....discussed with contractor and general at job existing panel needs addressed-non rated breaker installed in panel, open knock out, and labelling needs fixed...currently occupied house...will be fixed and rough inspection will be scheduled tomorrow or stop work order will be posted for safety issues
|