Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-03130
StatusFinaled
Name SUBLIME ELECTRIC LLC
Site Address 10704 W OVERLAND RD
Project NameHOOLIGANS TENANT IMPROVEMENT
Customer NumberHooligans
ePlanReviewNo
Description
Alteration: Provide wiring for kitchen/bathroom remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/25/201910/28/201910/28/2019APASS
DetailsTom Saunders
Call Luke ###-#### on your way and with any questions please. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan...
corrections made-circuit directory and neutral seperation

connected load re-engineered by engineer to show full connected load of existing business and new appliances-meets requirements...future loads added by neighboring business will need addressed at that time...ID Power is aware of issue
Final10/23/201910/24/201910/24/2019AFAIL
DetailsRock A. Hudson
There will people there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan A 200 amp disconnect has been installed to replace a 100 amp disconnect. Change out was completed after hours and reconnected by electrical contractor.
215.2- Feeders shall be sized as per load calculation in parts III, IV, V of artical 220. As per engineer drawing feeders shall be sized to carry 786 amps. 600 KCMIL aluminum installed rated at 340 amps. Feeder in question feeds 2 150amp disconnects and the 200 amp disconnect. Additional 100 amp taps out of main disconnecting means.

250.24(A)(5)- The grounded conductor shall not be connected to non-current carrying metal parts on load side of service disconnecting means.
408-4- Circuit directory shall be complete.
Electrical Rough-In9/23/20199/24/20199/24/2019APASS
DetailsRock A. Hudson
Call Luke with any questions at ###-#### Phone #: ###-#### Inspection requested via web by Clayton Morgan
Hardlids rough in ok cover
Electrical Rough-In9/20/20199/20/20199/20/2019PPASS
DetailsRock A. Hudson
There will be someone there. If you have any questions please feel free to contact Luke ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Missing exhaust fan in bath. Walls only rough in ok cover
Electrical Rough-In9/18/20199/19/20199/19/2019APART
DetailsRock A. Hudson
There will be someone there. If you have any questions please feel free to contact Fred ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Kitchen area only rough in ok cover