Final | 12/3/2019 | 12/3/2019 | 12/3/2019 | P | PASS |
Mark Moncarr
|
|
|
Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman Corrections made. Ok final.
|
Final | 11/25/2019 | 11/26/2019 | 11/26/2019 | A | FAIL |
Rock A. Hudson
|
|
|
garge code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman 110.3- Unable to located Christmas GFCI device, Back patio receptacle not working. 314.16- Boxes shall have adequate space for conductor fill installed. Kitchen island receptacle 11.25 cubic inches installed in a 8 cubic inch box. * Kitchen appliance/ freezer circuit marked do not turn on?
|
Electrical Rough-In | 10/16/2019 | 10/17/2019 | 10/17/2019 | A | PASS |
Rock A. Hudson
|
|
|
Floor heat. Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman Master bath floor heat rough in ok cover
|
Rough-In Permanent Service | 8/21/2019 | 8/26/2019 | 8/26/2019 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman Ok cover. Looked at on 8/23/19, only a couple of rooms left to make-up.
|
Rough-In Permanent Service | 8/23/2019 | 8/23/2019 | 8/23/2019 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman p/s u/g n ok
|