DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/3/201912/3/201912/3/2019PPASS
DetailsMark Moncarr
Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman Corrections made. Ok final.
Final11/25/201911/26/201911/26/2019AFAIL
DetailsRock A. Hudson
garge code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman
110.3- Unable to located Christmas GFCI device, Back patio receptacle not working.
314.16- Boxes shall have adequate space for conductor fill installed. Kitchen island receptacle 11.25 cubic inches installed in a 8 cubic inch box. * Kitchen appliance/ freezer circuit marked do not turn on?
Electrical Rough-In10/16/201910/17/201910/17/2019APASS
DetailsRock A. Hudson
Floor heat. Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman
Master bath floor heat rough in ok cover
Rough-In Permanent Service8/21/20198/26/20198/26/2019APASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Emmet Bushman Ok cover. Looked at on 8/23/19, only a couple of rooms left to make-up.
Rough-In Permanent Service8/23/20198/23/20198/23/2019APASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Emmet Bushman p/s u/g n ok