Final | 9/26/2019 | 9/27/2019 | 9/27/2019 | A | PASS |
Eric Story
|
|
|
Ready for final. Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin Occ card signed Final ok
|
Electrical Rough-In | 9/25/2019 | 9/25/2019 | 9/25/2019 | P | PASS |
Mark Moncarr
|
|
|
Ready for ceiling inspection. Thank You! Phone #: ###-#### Inspection requested via web by Kelly Felin Ok cover ceiling throughout. Waiting on 3 pendants to come in so boxes can be set in reception area.
|
Electrical Rough-In | 9/23/2019 | 9/23/2019 | 9/23/2019 | P | CANC |
Tom Saunders
|
|
|
Ready for rough in ceiling grid inspection Phone #: ###-#### >> Inspection requested via web by Kelly Felin Inspection cancelled from web by: Kelly Felin
|
Electrical Rough-In | 8/28/2019 | 8/28/2019 | 8/28/2019 | P | PASS |
James Ady
|
|
|
Walls only rough in. Front door is open. Contractor to fire seal penetrations on fire wall and will have ready for ceiling inspection. Phone #: ###-#### Inspection requested via web by Kelly Felin Corrections made rough in ok
|
Electrical Rough-In | 8/26/2019 | 8/27/2019 | 8/27/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Walls are ready for rough in inspection. Front door is open. Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin 300.21- Penetration in 2 hr fire wall shall be maintained. Low volt shall be installed in a 2 hr rated box, and repair round holes in upper wall to maintain 2 hr rated wall as per BLD permit. 300.4- Raceways and cables shall not be installed with in 1 1/4" of framing surface. ' 330.12- MC cable shall not be installed where subfect to damage. Do not secure on interior of 2x4 studs.
|