Permit Information
Permit NumberELE19-03198
StatusFinaled
Name K-F ELECTRIC
Site Address 8239 W FRANKLIN RD
Project Name 
Customer Number19-176
ePlanReviewNo
Description
Alteration: wiring for new tenant includes new lights,outlets per NEC
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/26/20199/27/20199/27/2019APASS
DetailsEric Story
Ready for final. Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin
Occ card signed
Final ok
Electrical Rough-In9/25/20199/25/20199/25/2019PPASS
DetailsMark Moncarr
Ready for ceiling inspection. Thank You! Phone #: ###-#### Inspection requested via web by Kelly Felin Ok cover ceiling throughout. Waiting on 3 pendants to come in so boxes can be set in reception area.
Electrical Rough-In9/23/20199/23/20199/23/2019PCANC
DetailsTom Saunders
Ready for rough in ceiling grid inspection Phone #: ###-#### >> Inspection requested via web by Kelly Felin Inspection cancelled from web by: Kelly Felin
Electrical Rough-In8/28/20198/28/20198/28/2019PPASS
DetailsJames Ady
Walls only rough in. Front door is open. Contractor to fire seal penetrations on fire wall and will have ready for ceiling inspection. Phone #: ###-#### Inspection requested via web by Kelly Felin Corrections made rough in ok
Electrical Rough-In8/26/20198/27/20198/27/2019AFAIL
DetailsRock A. Hudson
Walls are ready for rough in inspection. Front door is open. Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin
300.21- Penetration in 2 hr fire wall shall be maintained. Low volt shall be installed in a 2 hr rated box, and repair round holes in upper wall to maintain 2 hr rated wall as per BLD permit.
300.4- Raceways and cables shall not be installed with in 1 1/4" of framing surface. '
330.12- MC cable shall not be installed where subfect to damage. Do not secure on interior of 2x4 studs.