Final | 8/28/2019 | 8/30/2019 | 8/29/2019 | A | FAIL |
Mark Moncarr
|
|
|
Denis-service off longer than 1 year-please call Denis with an approx meet time as he''s going to come in from Ketchum Phone #: ###-#### Will need to hire a licensed electrical contractor for various items that need to be corrected. 1. Verify equipt ground for panel. Cant tell if rigid or PVC. 2. KO seals needed in J-box to right of panel. 3. Verify different brkr brands can be used with panel. 4. Remove misc extra wiring in J-box. 5. Verify GEC
|