Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-03270
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 611 S 8TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Install feeder wire in existing conduit, install inline fuse assemblies at base of pole, install ground rod in power HH, extend existing power and data 1" RGC conduits up the pole.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/26/20199/27/20199/27/2019APASS
DetailsRock A. Hudson
Mini cell site inspection
Contact Alex Ybarra
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
Final9/26/20199/26/20199/26/2019AFAIL
DetailsRock A. Hudson
Final inspection for mini cell site.
Contact Alex Ybarra
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
250.24- A grounding electrode conductor shall be connected to the grounded conductor at the service main discnnecting means. Grounds and neutrals seperated at time of inspection.
Electrical Rough-In9/12/20199/13/20199/13/2019APASS
DetailsRock A. Hudson
Underground Inspection
Contact Alex Ybarra
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Under ground rough in ok cover
Electrical Rough-In9/12/20199/12/20199/12/2019ACANC
DetailsRock A. Hudson
Underground Inspection.
Contact Alex Ybarra
Thank you, Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek