Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-03472
StatusFinaled
Name TOTAL PRECISION ELECTRIC LLC
Site Address 1102 E BOISE AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Service upgrade
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/19/20199/20/20199/20/2019APASS
DetailsJames Ady
Man door garage code 1224 for entry Phone #: ###-#### Inspection requested via web by Tyler Ridley final ok
Final9/16/20199/17/20199/17/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tyler Ridley
110.3- Open ground shown on east garage wall receptacle.
250.24(A)(1)- Grounding electrode conductor shall be connected to the grounded conductor at the service disconnecting means. At time of inspection bonding of neutral done in panel on load side of service disconnecting means. Grounded conductor shall not be connected to non-current carrying metal parts on load side of service disconnecting means as per 250.24(A)(5).
Called number provided and reached someone named Brandy, did not leave message, not sure if right party.
Rough-In Permanent Service9/16/20199/16/20199/16/2019PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Tyler Ridley....
installing in panel board (same size) and up grading grounding
rough in of garage outlets, new 4 wire to range, and FGCI protection where needed
p/s o/h reconnect ok