Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-03496
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 1100 W IDAHO ST
Project Name 
Customer Number3921
ePlanReviewNo
Description
Temporary Power Pole: One Meter - one location.
1200A Main Electrical gear, conduit, wire (1) spider box on each floor, SOOW cords, light strings in main corridors and stairwells, (2) large area lights on each floor, 600A 480V crane connection, 100A 208V job trailer connectio
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service10/8/201910/9/201910/9/2019APASS
DetailsRock A. Hudson
Contact electrician on-site Shawn Evins.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek t/s u/g n ok
Temporary Service10/4/201910/7/201910/7/2019PFAIL
DetailsRock A. Hudson
Contact electrical on-site Shawn Evins.
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
230.95(C)- Ground fault performance test shall be performed on all service disconnecting means rated 150 or more volts to ground and 1000 amps for greater.
Informed must have a core and shell permit, when temp power passes that permit automaticly finals out.
Electrical Rough-In10/7/201910/7/201910/7/2019PPASS
DetailsRock A. Hudson
Contact electrical on-site Shawn Evins.
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Ground ring and lightning arrest welds rough in ok cover
Electrical Rough-In9/20/20199/23/20199/23/2019APASS
DetailsRock A. Hudson
Uffer ground inspection for the Crane Power.
Contact Shawn Evins.
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Item noted rough in ok cover