Final | 1/24/2020 | 1/24/2020 | 1/24/2020 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David McClellan...ok to final
|
Final | 1/23/2020 | 1/23/2020 | 1/23/2020 | P | NR |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David McClellan... post light needs completed...contractor informed
|
Rough-In Permanent Service | 11/27/2019 | 11/29/2019 | 11/29/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by David McClellan Service inspected by 363 on 10/22/19. p/s u/g n ok
|
Electrical Rough-In | 10/22/2019 | 10/22/2019 | 10/22/2019 | P | PASS |
Tom Saunders
|
|
|
adding 2 smokes outside bedrooms Phone #: ###-#### Inspection requested via web by David McClellan...corrections made rough ok to cover p/s u/g new ok
|
Electrical Rough-In | 10/21/2019 | 10/22/2019 | 10/22/2019 | A | FAIL |
Daryl DeGrange
|
|
|
fireplace is in. other corrections done Phone #: ###-#### Inspection requested via web by David McClellan Original corrections completed, Building code requires smoke/carbon detectors install outside sleeping areas
|
Electrical Rough-In | 10/15/2019 | 10/15/2019 | 10/15/2019 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David McClellan... 1) fireplace shall be installed for rough-in inspection 2) manufacturers rating on connector used at panel for branch circuits is rated for no more than 2 NM cables-RC50 3) Foyer wiring - 210.52(I)...3ft wall space needs outlet..2 places
|