Final | 1/14/2020 | 1/15/2020 | 1/15/2020 | A | PASS |
Tom Saunders
|
|
|
Garage Code 4053 Phone #: ###-#### Inspection requested via web by Dean Gernaat... ok to final
|
Rough-In Permanent Service | 9/26/2019 | 9/30/2019 | 9/30/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat Corrections complete, fan/ light combo shown is shower will be a recessed can. Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 9/24/2019 | 9/25/2019 | 9/25/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Dean Gernaat 110.3- Fan/ light combo shown on print for master shower listing shall be verified. 250.68- Connection to concrete encased electode shall remain accessible. mud ring missing. 300.4- Wher NM cable passes thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage. Master bath near shower. 334.30- NM supports shall not exceed 4 1/2'. Garage tall bay. 424.28- Over current protection for furnace shall be 20 amp as per nameplate. 15 amp installed
|