Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberELE19-03740
StatusFinaled
Name TDR ELECTRIC
Site Address 4405 E PARKCENTER BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: new
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/16/201912/16/201912/16/2019PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
Rough-In Permanent Service10/3/201910/3/201910/3/2019APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Therrin Robertson Corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service10/2/201910/2/201910/2/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Therrin Robertson
210.52(A)(2)- Family room area above 24" tall 8' wide cabinet shall be concidered wall space and shall have receptacles installed. Receptacles shall be located below 5'6".
250.148- Where NM is spliced in a metal box the equipment grounding conductors shall be connected to the box. Pancake boxes.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage. Master bath across from shower. and up front bed. marked with an X.
300.15- NM cable shall terminate in a box. Patio light not stuffed in box.
334.23- Where nm cable is run in attic within 7' of attic access they shall be protected from damage by guard strips. Garage.