Permanent Service | 10/22/2019 | 10/23/2019 | 10/23/2019 | A | PASS |
Rock A. Hudson
|
|
|
door code 6290 Phone #: ###-#### Inspection requested via web by Greg Idsinga Range wire has been removed from breaker and has been cut off at the entrance to panel. p/s o/h rec ok
|
Permanent Service | 10/8/2019 | 10/8/2019 | 10/8/2019 | P | FAIL |
Rock A. Hudson
|
|
|
service off for a year lock box 6290 Phone #: ###-#### Inspection requested via web by Greg Idsinga 230.27- Service mast shall be securely mounted in place. Upper strap secured to a place of siding that has started to lift off house. 230.62- Panel cover shall be secured in place. No screw holding panel cover in place. 300.15- All conductor splices shall be contained in a box. Due to multiple open splices in range wire in crawl space either install a box at each splice point or replace with new wire.
|