Final | 6/15/2020 | 6/16/2020 | 6/16/2020 | A | PASS |
Tom Saunders
|
|
|
Access code is the address # Phone #: ###-#### Inspection requested via web by jamie berg...corrections made...ok to final
|
Final | 6/11/2020 | 6/11/2020 | 6/11/2020 | P | FAIL |
Tom Saunders
|
|
|
Call Jay Bedsole for access ###-#### Phone #: ###-#### Inspection requested via web by jamie berg... 1) incandescent and LED light fixtures shall be a minimum of 12 inches off shelf in closets..dwn stairs 2) outlet boxes shall be flush with mounting surface or sit no more than 1/4 inch back...kitchen counter outlets 3) receptacles shall be firmly attached to outlet box...kitchen counter recps 4) hardwired appliances shall have disconnects within sight or lockouts on OCPD..D/W and WH 5) knock out in panel needs addressed...breaker installed or blank installed 6) garage receps shall have GFCI protection..back wall of garage
|