Permit NumberELE19-03876
StatusFinaled
Name ATKINS ELECTRIC LLC
Site Address 222 S BROADWAY AVE
Project Name 
Customer Number1934
ePlanReviewNo
Description
Alteration: Fitness room addition.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/11/201912/11/201912/11/2019PPASS
DetailsEric Story
Outside egress light on the other side of the sidewalk, hooked up (see notes from previous final inspection.

Contact on project, Albert ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins
EC stated exposed wires are for fire alarm system, Also stated egress is across th way for court yard.
Final12/9/201912/10/201912/10/2019AFAIL
DetailsRock A. Hudson
Any questions, call Don (###-####) or Albert (###-####) Phone #: ###-#### Inspection requested via web by Bryan Atkins
* Outdoor egress light missing as noted on page 1 noted 16 of print. Exit to court yard.
300.15- All wiring shall terminate in a box. Exposed splice below exit sign main entrance.
Electrical Rough-In11/12/201911/13/201911/13/2019APASS
DetailsJames Ady
Soffits Phone #: ###-#### Inspection requested via web by Bryan Atkins Soffits only ok to cover
Electrical Rough-In11/4/201911/5/201911/5/2019APASS
DetailsJames Ady
Inspection for the ceiling; fire caps/covers installed.
Journeyman, Don Hampton, ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins Ceiling only ok to cover
Electrical Rough-In10/30/201910/31/201910/31/2019APART
DetailsJames Ady
Ceiling inspection. Journeyman Don Hampton ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins Walls only at this time. Cans in ceiling need to have "fire hats" installed
Electrical Rough-In10/25/201910/28/201910/28/2019APART
DetailsRock A. Hudson
Partial rough-in. Phone #: ###-#### Inspection requested via web by Bryan Atkins
BCC 4-05-23- Reminded contractor it is unlawful to cover in any way electrical wiring or equipment without first having same inspected by an electrical inspector. General contractor pressuring to cover ready or not.
HR chase and 4'x4' upper corners around room for soffit construction rough in ok cover.
Electrical Rough-In10/9/201910/10/201910/10/2019PPASS
DetailsRock A. Hudson
Underground rough-in inspection. For questions, please call Don Hampton, ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins
Floor boxes have seperation of low volage and line voltage provided.
Underslab and floor boxes rough in ok cover