Permit Information
Permit NumberELE19-03927
StatusFinaled
Name AMP ELECTRIC
Site Address 6048 S STURGEON WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Rough In
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/21/201911/22/201911/22/2019APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Greg Traudt...ok to final
Rough-In Permanent Service10/15/201910/15/201910/15/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Greg Traudt
Rough in ok cover p/s u/g n ok
Rough-In Permanent Service10/14/201910/15/201910/15/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Greg Traudt
300.4- Wher NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates.
334.23- NM cable run on trusses within 7' of attic access shall be protected by guard strips.
334.30- NM cable shall be secured within 8" of island receptacle.