Final | 11/11/2019 | 11/12/2019 | 11/12/2019 | A | PASS |
Mark Moncarr
|
|
|
I need to request inspector Mark Moncarr Inspection requested via web by BRS Permitting Ok final. This is a supply side connection. It falls under the 6 disconnect rule as there is no main breaker. All labeling present.
|
Final | 10/31/2019 | 11/1/2019 | 11/1/2019 | A | FAIL |
Mark Moncarr
|
|
|
Mierins Rozentals is the on site contact Phone #: ###-#### Inspection requested via web by BRS Permitting 100a service, cannot verify buss rating. 2 pole 25 installed. Needs to be a 2 pole 20a brkr.
|
Electrical Rough-In | 10/30/2019 | 10/31/2019 | 10/31/2019 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by BRS Permitting Ok cover. Items UL listed.
|