Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE19-04131
StatusIssued
Name LEA ELECTRIC LLC
Site Address 959 W FRONT ST
Project Name 
Customer Number3929
ePlanReviewNo
Description
New: Full electrical installation for Restaurant T.I. including new under ground/slab work, thermoslab heating cable, conduit, wiring, panels, switchgear, lighting, lighting controls, recepts, fire alarm and teledata.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In3/17/20203/18/20203/18/2020APASS
DetailsRock A. Hudson
Rough in inspection for vestibule and reception walls and ceilings. Show window areas above mullions. Raised seating wood frame walls. Phone #: ###-#### Inspection requested via web by John Mittleider
Areas noted rough in ok cover.
Conference3/10/20203/11/20203/11/2020APASS
DetailsRock A. Hudson
Discuss whether a drain pan will be necessary over garage panel boards. Phone #: ###-#### Inspection requested via web by John Mittleider Discussed requirement for drip protection of panel boards for new equipment located in baseement. Nearest pipe to dedicated electrical space is a non-pressurized drain line. Minimal protection required for drip type leak, spray hazard not present in this line.
Electrical Rough-In3/10/20203/10/20203/10/2020PPASS
DetailsEric Story
Cover inspection for bar ceiling, hostess ceiling, bar dining wall and drop ceiling. Review acceptability of drain pan over garage panels. Phone #: ###-#### Inspection requested via web by John Mittleider
Areas as noted on print ok to cover
*looked at area in garage for work clearences with water pipes over panelboard a conference will be requested as a pan above panelbord will approach work clearences as per 110.26 needing 6' above
Electrical Rough-In3/2/20203/3/20203/3/2020APASS
DetailsEric Story
Rough in inspection for restrooms and banquet rooms walls and ceilings. Inspect ceiling of lower soffit surrounding Upper Dining area. Phone #: ###-#### Inspection requested via web by John Mittleider
Areas as noted on print ok to cover
Electrical Rough-In2/26/20202/26/20202/26/2020PPASS
DetailsRock A. Hudson
Wall rough in inspection. North of column A-D. West of serving counter wall. Column A-4. Phone #: ###-#### Inspection requested via web by John Mittleider
Areas noted on contractor print walls only rough in ok cover.
Electrical Rough-In1/31/20202/3/20202/3/2020APASS
DetailsRock A. Hudson
Inspect raceways under slab in dining rooms , restaurant and bar areas. Phone #: ###-#### Inspection requested via web by John Mittleider Areas noted plus private dining under slab rough in ok cover.
Electrical Rough-In1/23/20201/23/20201/23/2020PPASS
DetailsRock A. Hudson
Under slab raceways in kitchen, coffee bar, restrooms, private dining areas Phone #: ###-#### Inspection requested via web by John Mittleider
Private dining not ready the rest listed underslab rough in ok cover.
Electrical Rough-In1/20/20201/21/20201/21/2020APART
DetailsRock A. Hudson
Wall inspection for 24” cement board rips from structural slab. Confirm requirements for show window receptacles. Phone #: ###-#### Inspection requested via web by John Mittleider Bottom 24" of walls as noted on contractor print for floor build up rough in ok cover.