Permit Information
Permit NumberELE19-04204
StatusFinaled
Name SZURGOT ELECTRIC
Site Address 1760 W SILVER CREST DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Whole house wiring
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/18/20206/19/20206/19/2020PPASS
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Barbara Szurgot No sign off card on site, final ok
Final6/17/20206/18/20206/18/2020AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.3- Pantry light not working. 250.94- An intersystem bond shall be installed for utilities. 314.25- All boxes and devices shall have covers. Areas with tile have cover and devices removed. 352.30- PVC service riser shall be secured with in 3' of meter base. 422.30- Appliances shall have an accessible disconnecting means. 110.25 lock outs acceptable. Dishwasher and micro. 680.51- Fountain shall have GFCI protection for pump
Electrical Rough-In4/6/20204/6/20204/6/2020PPASS
DetailsMark Moncarr
Floor heat inspection Phone #: ###-#### Inspection requested via web by Barbara Szurgot Ok cover floor heat mstr.
Rough-In Permanent Service11/26/201911/26/201911/26/2019PPASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Corrections made...p/s u/g n ok
Electrical Rough-In11/22/201911/25/201911/25/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Box front garage light.
Secure NM above small panel.
NM sheathing shall enter boxes a min of 1/4"
Torque main bonding jumper screws.
Secure dryer box.
Recessed can covers shall be completely installed, up loft, above master vanity, kitchen.
Furnace temp hook up shall be in a box.
no more than 12' between receptacle outlets in S.E. rm.