Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-04238
StatusFinaled
Name APEX ELECTRICAL SERVICES
Site Address 2480 N MAPLE GROVE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Replace damaged service. Repair wiring in bedroom
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/6/201912/6/201912/6/2019PPASS
DetailsTom Saunders
Ryan Phone #: ###-####...panel complete and rewire of damaged wall..ok to final
Rough-In Permanent Service11/6/201911/7/201911/7/2019APASS
DetailsTom Saunders
code 4810 Phone #: ###-#### Inspection requested via web by Ryan Wake...
minimum corrections made to get service turned back on and cover rough-in of new walls
other corrections need addressed by final
rough ok to cover
p/s o/h reconnect ok
Rough-In Permanent Service11/5/201911/6/201911/6/2019AFAIL
DetailsRock A. Hudson
Unoccupied. Lock box on back door code 4810 Phone #: ###-#### Inspection requested via web by Ryan Wake
250.53(A)(2)- Unable to verify supplemental ground rod, covered by pavers.
300.4- nail plates needed in bedroom north west corner.
BCC 4-05-32- No code violation to be retained. Existing NM cables run through short pieces of PVC with ends open with exposed NM cable.