Permit Information
Permit NumberELE19-04338
StatusFinaled
Name ENERGY ENTERPRISE GROUP LLC
Site Address 505 W IDAHO ST Unit: 100
Project Name 
Customer Number781
ePlanReviewNo
Description
Electrical for restaurant TI
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/13/20202/13/20202/13/2020PPASS
DetailsMark Moncarr
Please call 30 mins prior as Kip is not on site. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ok final. Verified egress works, and fly fan is running.
Final2/7/20202/7/20202/7/2020PPART
DetailsJames Ady
Temp Final
Please call 30 mins prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton "Fly" fan on rear 5th st entry Needs installed, NE Egress light on Idaho st not functioning tco only ok
Electrical Rough-In1/16/20201/17/20201/17/2020APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Discussed GFCI protection of kitchen receptacles, All receptacles will require GFCI protection in commercial kitchens as per 210.8(B). 3 pole appliance ok to hardwire and provide a disconnecting means if contractor chooses due to GFCI devices are not available at 35 amp rating.
Kitchen grid rough in ok cover.
Conference12/9/201912/9/201912/9/2019APASS
DetailsRock A. Hudson
Kip is the site contact and his number is ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Discussed pathway to roof top units. Access will be provided for levels 3, 4, 5, will have to fish MC cable approx 12' thru level 2. Wiring method ok as long as supporting is complete where accessible.
Electrical Rough-In11/21/201911/21/201911/21/2019APASS
DetailsRock A. Hudson
please call 30 minutes ahead if possible. Kip is the contact at ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Rough in of pathways encasing mc rough in ok cover
Electrical Rough-In11/12/201911/12/201911/12/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Due to shortage of materials all recessed luminaires to be listed cut-in type cans. Soffits and hardlids rough in ok cover
Electrical Rough-In11/8/201911/12/201911/12/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Walls only rough in ok cover