Final | 2/13/2020 | 2/13/2020 | 2/13/2020 | P | PASS |
Mark Moncarr
|
|
|
Please call 30 mins prior as Kip is not on site. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ok final. Verified egress works, and fly fan is running.
|
Final | 2/7/2020 | 2/7/2020 | 2/7/2020 | P | PART |
James Ady
|
|
|
Temp Final Please call 30 mins prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton "Fly" fan on rear 5th st entry Needs installed, NE Egress light on Idaho st not functioning tco only ok
|
Electrical Rough-In | 1/16/2020 | 1/17/2020 | 1/17/2020 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed GFCI protection of kitchen receptacles, All receptacles will require GFCI protection in commercial kitchens as per 210.8(B). 3 pole appliance ok to hardwire and provide a disconnecting means if contractor chooses due to GFCI devices are not available at 35 amp rating. Kitchen grid rough in ok cover.
|
Conference | 12/9/2019 | 12/9/2019 | 12/9/2019 | A | PASS |
Rock A. Hudson
|
|
|
Kip is the site contact and his number is ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed pathway to roof top units. Access will be provided for levels 3, 4, 5, will have to fish MC cable approx 12' thru level 2. Wiring method ok as long as supporting is complete where accessible.
|
Electrical Rough-In | 11/21/2019 | 11/21/2019 | 11/21/2019 | A | PASS |
Rock A. Hudson
|
|
|
please call 30 minutes ahead if possible. Kip is the contact at ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rough in of pathways encasing mc rough in ok cover
|
Electrical Rough-In | 11/12/2019 | 11/12/2019 | 11/12/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Due to shortage of materials all recessed luminaires to be listed cut-in type cans. Soffits and hardlids rough in ok cover
|
Electrical Rough-In | 11/8/2019 | 11/12/2019 | 11/12/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Walls only rough in ok cover
|