Final | 2/21/2020 | 2/24/2020 | 2/24/2020 | A | PASS |
Rock A. Hudson
|
|
|
Garage code 1974, thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
Final | 2/20/2020 | 2/21/2020 | 2/21/2020 | A | FAIL |
Rock A. Hudson
|
|
|
door code is 1974 Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.52(A)(2)- Receptacle outlets shall be installed with in 6' each side of fireplace wall space. Such receptacles shall not be located in cabinets. 210.52(C)- Pantry counter top shall have receptacle outlets installed so that at no point on counter is more than 24" from a receptacle outlets. 250.94- A intersystem bond bar shall be installed to bond communication systems. 314.21- Drywall shall be repaired around RV receptacle box so gap around box does not exceed 1/8". 406.5(D)- Garage door opener receptacle shall have a cover installed so receptacle is flush with cover plate. 410.16(A)- Luminaires located in master clothes closet shall have totally enclosed lamps.
|
Rough-In Permanent Service | 11/26/2019 | 11/27/2019 | 11/27/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 11/26/2019 | 11/26/2019 | 11/26/2019 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn... 1..exhaust fans need hooked up/completed..110.3 2..boxes need installed in low volt panel...verify grounding steel boxes
|