Electrical Rough-In | 12/4/2019 | 12/5/2019 | 12/5/2019 | A | PASS |
James Ady
|
|
|
Electrician: Brendan Phone #: ###-#### Inspection requested via web by Same Electric Rough in ok. Note: 2 receps have been added. Foot print of hot tub unknown. Receps shall be at least 6ft from edge of tub as per 680.22 (Koi pond recep may be to close.) Breakers have been relocated in panel and must be relabeled by final as per 408.4
|