Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-04674
StatusFinaled
Name SOESBE ELECTRIC LLC
Site Address 5400 W EMERALD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Replacing main disconnect equipment to building
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/19/201912/19/201912/19/2019PPASS
DetailsRock A. Hudson
Got the third bonding jumper in. Ask for Robert or Cassie they will take you to the back room thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe
Final ok
Permanent Service12/4/201912/8/201912/7/2019PPASS
DetailsRock A. Hudson
After hours inspection Sun. 12/8 PM; contact Trevor Soesbe ###-#### p/s u/g rec ok
Conference12/4/201912/6/201912/6/2019PPASS
DetailsRock A. Hudson
Call me when your headed that way and I’ll meet you there thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe
Discussed the changing of 800 amp service, Available fault current for 25k rated mains, grounding electrode system, Fire sprinkler and water main both underground metal water pipes plus has ground rod at I-Line location.
Final12/4/201912/9/201912/4/2019ACANC
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Trevor Soesbe //12/4/19 cancel inspection per Daryl D., inspection needed is scheduled for 12/8 //leg