Permit Information
Permit NumberELE19-04755
StatusFinaled
Name PRIORITY ELECTRIC
Site Address 1100 W FRONT ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: New power and lighting for bar remodel.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/11/20202/11/20202/11/2020PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins Final ok
Final2/6/20202/7/20202/7/2020PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
210.8- All GFCI devices shall be located in a readily accessible location. Soffit receptacle.
210.8(B)(2)- All receptacle outlets 150 volts to ground up to 100 amp located in kitchen areas shall have GFCI protecion, 3 2 pole receptacles.
210.8(B)(5)- Bar area receptacles located with in 6' of a sink shall have GFCI protection. Inside and outside of bar.
210.62- All show window receptacles shall be located with in 18" of top of windows.
Permanent Service1/29/20201/29/20201/29/2020PPASS
DetailsRock A. Hudson
Replacing existing meter and panel with new meter and sub panels. Phone #: ###-#### Inspection requested via web by Tom Jenkins p/s o/h rec ok
Electrical Rough-In1/14/20201/15/20201/15/2020APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Exterior entrance soffit rough in ok cover
Electrical Rough-In1/14/20201/15/20201/14/2020PCANC
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Tom Jenkins Inspection cancelled from web by: Tom Jenkins
Electrical Rough-In12/26/201912/27/201912/27/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Rest of walls rough in ok cover.
Electrical Rough-In12/18/201912/18/201912/18/2019PPART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
North bar wall only rough in ok cover