Final | 2/11/2020 | 2/11/2020 | 2/11/2020 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Final ok
|
Final | 2/6/2020 | 2/7/2020 | 2/7/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins 210.8- All GFCI devices shall be located in a readily accessible location. Soffit receptacle. 210.8(B)(2)- All receptacle outlets 150 volts to ground up to 100 amp located in kitchen areas shall have GFCI protecion, 3 2 pole receptacles. 210.8(B)(5)- Bar area receptacles located with in 6' of a sink shall have GFCI protection. Inside and outside of bar. 210.62- All show window receptacles shall be located with in 18" of top of windows.
|
Permanent Service | 1/29/2020 | 1/29/2020 | 1/29/2020 | P | PASS |
Rock A. Hudson
|
|
|
Replacing existing meter and panel with new meter and sub panels. Phone #: ###-#### Inspection requested via web by Tom Jenkins p/s o/h rec ok
|
Electrical Rough-In | 1/14/2020 | 1/15/2020 | 1/15/2020 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Exterior entrance soffit rough in ok cover
|
Electrical Rough-In | 1/14/2020 | 1/15/2020 | 1/14/2020 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Tom Jenkins Inspection cancelled from web by: Tom Jenkins
|
Electrical Rough-In | 12/26/2019 | 12/27/2019 | 12/27/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Rest of walls rough in ok cover.
|
Electrical Rough-In | 12/18/2019 | 12/18/2019 | 12/18/2019 | P | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins North bar wall only rough in ok cover
|