Final | 1/22/2020 | 1/22/2020 | 1/22/2020 | P | PASS |
Tom Saunders
|
|
|
Jay Phone #: ###-####...ok to final
|
Final | 1/6/2020 | 1/6/2020 | 1/6/2020 | P | NR |
Tom Saunders
|
|
|
Jay Phone #: ###-####... power required to be on at residence before final can be given
|
Permanent Service | 12/27/2019 | 12/27/2019 | 12/27/2019 | P | PASS |
Tom Saunders
|
|
|
call for access // Jay Phone #: ###-####... grounding/bonding verified...in crawl mini split hookup and front light required by final p/s u/g new ok
|
Permanent Service | 12/20/2019 | 12/20/2019 | 12/20/2019 | P | FAIL |
Mark Moncarr
|
|
|
Jay Phone #: ###-#### Corrections were not made. Unit was locked, could not verify GEC, wire in front was not safed off.
|
Final | 12/18/2019 | 12/18/2019 | 12/18/2019 | P | FAIL |
Tom Saunders
|
|
|
Jay Phone #: ###-####... 1) not ready for final...inspection needs to be permanent service - final once power is on at building 2) unable to verify grounding for service uffer ground? ground rods? 3) riser needs strapped to manufacturers instructions and within 3ft of meter/panel 4) required bonding of building unverifiable individual steel containers 5) no code violation shall be retained - exposed NMB cable on exterior of building...missing front light
|