Final | 12/19/2019 | 12/20/2019 | 12/20/2019 | A | FAIL |
Daryl DeGrange
|
|
|
Call Chris @ ###-#### to gain access to panel Phone #: ###-#### Inspection requested via web by Seth Stears Corrections not all completed, Available Fault current required to be posted on service gear (CT can)
|
Permanent Service | 12/20/2019 | 12/20/2019 | 12/20/2019 | P | PASS |
Daryl DeGrange
|
|
|
Available fault current 20,818 amps OCP device rated at 22,000 amps owner will post placard today p/s u/g rec ok
|
Final | 12/18/2019 | 12/18/2019 | 12/18/2019 | P | FAIL |
Tom Saunders
|
|
|
Inspection so that they can turn power back on to a building that has been without power for over a year per Idaho Power''s request. Phone #: ###-#### Inspection requested via web by Seth Stears... 1...access to electrical rm is required to verify/inspect panels 2..AFC label is required to energize service 3..required grounding of service-unable to verify
recommend contractor meet for inspection being a carwash
|