Final | 2/3/2020 | 2/3/2020 | 2/3/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Contact: Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden *Address is 802 W. Bannock, need corrected prior to final. 110.14- Unused breaker spaces shall be closed by approved means. 314.25- All boxes shall have covers installed, most removed due to painting. 408.4- Circuit directories shall be present and accurate.
|
Electrical Rough-In | 1/21/2020 | 1/21/2020 | 1/21/2020 | P | PASS |
Rock A. Hudson
|
|
|
Attn: Caleb Burke... ceiling inspection please... Address should be 802 W Bannock, spoke with Brittney, she could find it to change it so waiting for call back from addressing Phone #: ###-#### Inspection requested via web by Deb Gooden Lighting retro, receptacle additions fished in. Grid rough in ok cover
|
Electrical Rough-In | 1/20/2020 | 1/21/2020 | 1/21/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Contact: Caleb Burke... ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Wrong address, should be 802 W Bannock, attach to building permit. open boxes and KO seals needed. Recall
|