Information based on query as of Thursday, June 27, 2024.
Permit Information
Permit NumberELE20-00188
StatusFinaled
Name DAKOTA ELECTRIC INC
Site Address 240 W IOWA ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Reroiute Baseboard heat to 2) ductless splitt units
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/3/20202/4/20202/4/2020APASS
DetailsJames Ady
If you need to check breakers there is a key in west disconnect inside disconnect. Phone #: ###-#### Inspection requested via web by shane miller corrections made final ok
Final1/31/20202/3/20202/3/2020AFAIL
DetailsJames Ady
Please inspect is there As early as possible please call ###-#### so he can arrive and open the door if needed Phone #: ###-#### Inspection requested via web by shane miller 440.22C Overcurrent shall not exceed manufacturer ratings. (25A max 30A installed Minnimum circuit ampacity is 23.8A. 25A breaker or fuses must be installed)
Final1/22/20201/23/20201/23/2020PCANC
DetailsEric Story
Phone # is for jeff- Please call to make sure he can let you in. Installed 2) new 30 amp circuits to future ductless splits to be installed . was hoping to get rough-in and final all at once. If You need to see units connected please advise and I can reschuedule after unit are in place. Thank you. Phone #: ###-#### Inspection requested via web by shane miller
No final at this point untyil units set and wired
Electrical Rough-In1/23/20201/23/20201/23/2020PPASS
DetailsEric Story
Phone # is for jeff- Please call to make sure he can let you in. Installed 2) new 30 amp circuits to future ductless splits to be installed . was hoping to get rough-in and final all at once. If You need to see units connected please advise and I can reschuedule after unit are in place. Thank you. Phone #: ###-#### Inspection requested via web by shane miller
Need to verify OCPD once units are installed
(panel has twin 30-30 installed at time of inspection...)