Final | 3/10/2020 | 3/11/2020 | 3/11/2020 | A | PASS |
James Ady
|
|
|
The homeowner will be home in the morning and has reported that HVAC did come out and replace the fittings for the mini split with the proper fittings. Please let me know if you have any questions. Thank you! Phone #: ###-#### Inspection requested via web by Dan Jennings Corrections made final ok
|
Final | 3/8/2020 | 3/9/2020 | 3/9/2020 | A | FAIL |
James Ady
|
|
|
The homeowner has stated that he will be home Monday morning. Please let me know if you have any questions. Thank you! Phone #: ###-#### Inspection requested via web by Dan Jennings 110.3B Jacketed MC shall terminate in a listed connector. (Mini split)
|
Final | 3/4/2020 | 3/6/2020 | 3/6/2020 | A | NH |
James Ady
|
|
|
The homeowner will be home Friday morning. The addition has a future second kitchen in it but the cabinets won''t be installed for years potentially. Everything is trimmed out except the microwave outlet because there isn''t a cabinet yet. Instead we installed a 4sq box with blank cover. The box is grounded and the wires saved off. Please let me know if you have any questions. Thank you! Phone #: ###-#### Inspection requested via web by Dan Jennings no answer at door no access
|
Final | 3/4/2020 | 3/6/2020 | 3/4/2020 | A | CANC |
James Ady
|
|
|
The homeowner will be home Friday morning. The addition includes a future second kitchen but the cabinets won''t be installed for years potentially. Everything is trimmed out except the microwave outlet which has a 4sq outlet with blank cover on it. Please let me know if you have any questions. Phone #: ###-#### >> Inspection requested via web by Dan Jennings Inspection cancelled from web by: Dan Jennings
|
Electrical Rough-In | 2/4/2020 | 2/5/2020 | 2/5/2020 | A | PASS |
James Ady
|
|
|
Good afternoon, we have addresses the shoddy staple work. Flat cables are now stalled flat, stackers have been installed at busy locations, and general quality of sta pl ling has been corrected. Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings Corrections made Master bed, Laundry room, Living room and Kitchen ok to cover.
|
Electrical Rough-In | 2/3/2020 | 2/4/2020 | 2/4/2020 | A | FAIL |
James Ady
|
|
|
Good evening, the homeowner will not be home but the side gate and side door to the addition will be open. This is for the rough in for the addition, the rough in for the kitchen remodel was already completed as well as the service upgrade. Please let me know if you have any questions! Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings 334.30 Flat NM cables shall not be securred on edge. 300.4D Cables shall not be secured less than 1 1/4in from face of framing. (Master bath 3 gang, Side entry 2 gang, Back slider 2 gang, Fan/ Fan light 2 gang)
|
Permanent Service | 1/30/2020 | 1/30/2020 | 1/30/2020 | P | PASS |
James Ady
|
|
|
Service is being upgraded to 200A from 100A. Requesting inspection so the customer can get their service re-energized. Thank you! Phone #: ###-#### Inspection requested via web by Dan Jennings p/s u/g rec ok
|
Electrical Rough-In | 1/17/2020 | 1/21/2020 | 1/21/2020 | P | PASS |
James Ady
|
|
|
This inspection request is just for the kitchen remodel portion of this work. The service upgrade and rough in for the addition have not been started yet. The kitchen is expanding about 3-4 feet north and getting new cabinets. Please give me a call if there are any questions.Also, the homeowner said they would be available in the afternoons by 2pm....possibly by 1pm. Thank you! Phone #: ###-#### Inspection requested via web by Dan Jennings kitchen only ok to cover
|