Final | 3/5/2020 | 3/5/2020 | 3/5/2020 | P | PASS |
Mark Moncarr
|
|
|
Got the electrical redone around the panel and grounded with two ground rods and refed 4 wires to each panel with grounds separated from neutrals. Also got service outlets added. Call with any questions thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe Ok final. Corrections made.
|
Final | 2/24/2020 | 2/25/2020 | 2/25/2020 | A | FAIL |
Mark Moncarr
|
|
|
Ran 6 dedicated circuits for mini splits and replaced lighting throughout units. Units are vacant code for doors is 123456 call with any questions thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe 1. Service recepts required for AC units on both sides of structure. 2. Remove and replace all non weather proof boxes and flex on back of structure with weather rated items. 3. For each sub panel on same structure with meter pack, assure 4 wire system and install 2 grd rods and grounding electrode conductor. 4. Weather rated labels for each AC disconnect confirming apt number.
|