Final | 4/15/2020 | 4/16/2020 | 4/16/2020 | A | PASS |
Mark Moncarr
|
|
|
corrections are made and ready for final. garage code 1976 Phone #: ###-#### Inspection requested via web by Brian Hughes Ok final.
|
Final | 4/14/2020 | 4/15/2020 | 4/15/2020 | A | FAIL |
Rock A. Hudson
|
|
|
garage code is 1976 if no one is there . please call with corrections. Phone #: ###-#### Inspection requested via web by Brian Hughes 110.3- 2 kitchen counter and island receptacles not working. 314.16- Adequate conductor space shall be installed for wire and devices installed. 8 cubic inch box installed for kitchen island with 11.25 of cubic inches installed. 422.30- A disconnecting means shall be provided for all hardwired appliances.
|
Electrical Rough-In | 3/12/2020 | 3/13/2020 | 3/13/2020 | A | PASS |
Mark Moncarr
|
|
|
This is for floor heat on electrical rough . please call if needed. thanks Phone #: ###-#### Inspection requested via web by Brian Hughes Ok cover floor heat mstr
|
Rough-In Permanent Service | 1/27/2020 | 1/29/2020 | 1/29/2020 | A | PASS |
Rock A. Hudson
|
|
|
please call with and corrections. Phone #: ###-#### Inspection requested via web by Brian Hughes General contractor to provide fire cover for outdoor recessed can in front entrance. Rough in ok cover p/s u/g n ok
|