Permit NumberELE20-00371
StatusFinaled
Name APEX ELECTRICAL SERVICES
Site Address 2313 S VIA PRIVADA LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: new home electrical
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/22/20207/23/20207/23/2020PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Ryan Wake Down bed GFCI is controlled by wall switch and protects outdoor recep. Air screens contorlled by wall switch Corrections made final ok
Final7/21/20207/22/20207/22/2020AFAIL
DetailsRock A. Hudson
Garage code 4908
Phone #: ###-#### Inspection requested via web by Ryan Wake 110.3- Equipment shall work as per instructions. Island counter top receptacles and down bed GFCI behind dor not working. 210.52(C)- Pantry counter top spaces shall have receptacle outlets installed so that not point on counter top is more than 24" from a receptacle outlet. 314.23- Island pop-up receptacle assemblies shall be secured in place.
* unable to verify a disconnecting means for air curtain.
Electrical Rough-In6/10/20206/11/20206/11/2020APASS
DetailsJames Ady
garage code 4908. Master bath floor heat rough in Phone #: ###-#### Inspection requested via web by Ryan Wake Master floor heat only ok to cover
Rough-In Permanent Service2/26/20202/27/20202/27/2020APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Ryan Wake Corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service2/25/20202/26/20202/26/2020AFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Ryan Wake 300.4A1 Bored holes less than1 1/4in from face of stud shall have nail plates(Master Bed right of sliding door emerging from crawl) 110.14A Acorn shall ensure a thoroughly good connection. (UFER)
Electrical Rough-In1/30/20201/31/20201/31/2020APASS
DetailsJames Ady
soffit cover inspection Phone #: ###-#### Inspection requested via web by Ryan Wake Soffits only ok to cover