Information based on query as of Monday, May 20, 2024.
Permit Information
Permit NumberELE20-00469
StatusFinaled
Name CAPITOL ELECTRIC
Site Address 9605 S EISENMAN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: 2000 amp service with 100 amp house panel and exterior lighting
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/15/20207/16/20207/16/2020APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Jim Williams final ok
Final6/30/20206/30/20206/30/2020PPART
DetailsJames Ady
Temporary Phone #: ###-#### Inspection requested via web by Jim Williams GFCI in bath not reseting, Exterior and parking lot lights missing. All life safety funtional Partial final ok
Permanent Service5/31/20206/1/20206/1/2020APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Jim Williams p/s u/g n ok
Permanent Service5/27/20205/28/20205/28/2020AFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Jim Williams 110.24 Available fault current shall be documented. 230.95C Performance testing. The ground fault protection system shall be performance tested when first installed onsite. 150V to ground or more and 1000A or more (2000A service only)
Electrical Rough-In5/27/20205/27/20205/27/2020APASS
DetailsJames Ady
4 light poles Phone #: ###-#### Inspection requested via web by Jim Williams Underground ok to cover
Electrical Rough-In5/6/20205/6/20205/6/2020PPASS
DetailsJames Ady
Underground Phone #: ###-#### Inspection requested via web by Jim Williams Site lighting underground and pole bases along back side of building ok to cover
Electrical Rough-In4/28/20204/28/20204/28/2020PPASS
DetailsEric Story
Public Works, Underground- JIm **cleared** Phone #: ###-####
U/G for site lights on Eisenman road ok to cover
Electrical Rough-In3/17/20203/17/20203/17/2020PPASS
DetailsJames Ady
Underground Phone #: ###-#### Inspection requested via web by Jim Williams Underground along interior perimeter for 480V sub panles and misc branch circuits. ok to cover
Electrical Rough-In2/10/20202/11/20202/11/2020APASS
DetailsJames Ady
Ufer ground Phone #: ###-#### Inspection requested via web by Jim Williams ufer ok to cover
Electrical Rough-In2/10/20202/10/20202/10/2020PFAIL
DetailsJames Ady
Ufer ground on NE of building Phone #: ###-#### Inspection requested via web by Jim Williams 2/0 copper ufer called for in one line. #4 installed install 2/0 and re-call