Final | 7/15/2020 | 7/16/2020 | 7/16/2020 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams final ok
|
Final | 6/30/2020 | 6/30/2020 | 6/30/2020 | P | PART |
James Ady
|
|
|
Temporary Phone #: ###-#### Inspection requested via web by Jim Williams GFCI in bath not reseting, Exterior and parking lot lights missing. All life safety funtional Partial final ok
|
Permanent Service | 5/31/2020 | 6/1/2020 | 6/1/2020 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams p/s u/g n ok
|
Permanent Service | 5/27/2020 | 5/28/2020 | 5/28/2020 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams 110.24 Available fault current shall be documented. 230.95C Performance testing. The ground fault protection system shall be performance tested when first installed onsite. 150V to ground or more and 1000A or more (2000A service only)
|
Electrical Rough-In | 5/27/2020 | 5/27/2020 | 5/27/2020 | A | PASS |
James Ady
|
|
|
4 light poles Phone #: ###-#### Inspection requested via web by Jim Williams Underground ok to cover
|
Electrical Rough-In | 5/6/2020 | 5/6/2020 | 5/6/2020 | P | PASS |
James Ady
|
|
|
Underground Phone #: ###-#### Inspection requested via web by Jim Williams Site lighting underground and pole bases along back side of building ok to cover
|
Electrical Rough-In | 4/28/2020 | 4/28/2020 | 4/28/2020 | P | PASS |
Eric Story
|
|
|
Public Works, Underground- JIm **cleared** Phone #: ###-#### U/G for site lights on Eisenman road ok to cover
|
Electrical Rough-In | 3/17/2020 | 3/17/2020 | 3/17/2020 | P | PASS |
James Ady
|
|
|
Underground Phone #: ###-#### Inspection requested via web by Jim Williams Underground along interior perimeter for 480V sub panles and misc branch circuits. ok to cover
|
Electrical Rough-In | 2/10/2020 | 2/11/2020 | 2/11/2020 | A | PASS |
James Ady
|
|
|
Ufer ground Phone #: ###-#### Inspection requested via web by Jim Williams ufer ok to cover
|
Electrical Rough-In | 2/10/2020 | 2/10/2020 | 2/10/2020 | P | FAIL |
James Ady
|
|
|
Ufer ground on NE of building Phone #: ###-#### Inspection requested via web by Jim Williams 2/0 copper ufer called for in one line. #4 installed install 2/0 and re-call
|